Humidity and Dew Point Calculator

Calculate relative humidity, dew point temperature, and absolute humidity from dry-bulb temperature and either a wet-bulb reading or a known relative humidity value.

Input Method

Temperatures

°C
°C
%
m

Formulas Used

1. Saturation Vapour Pressure — Buck Equation (1981)

es(T) = 6.1121 · exp[(18.678 − T/234.5) · T / (257.14 + T)]

T in °C, es in hPa. Valid from −40 °C to +60 °C.

2. Actual Vapour Pressure from RH

e = (RH / 100) · es(Tdb)

3. Actual Vapour Pressure from Wet-Bulb — Sprung Formula

e = es(Twb) − γ · (Tdb − Twb)

where γ = 0.000665 · P (psychrometric constant, hPa/°C) and P is atmospheric pressure.

4. Atmospheric Pressure from Elevation — Barometric Formula

P = 1013.25 · (1 − 2.25577×10⁻⁵ · h)5.25588

5. Dew Point — Magnus Inversion

Td = 243.04 · ln(e / 6.1121) / [17.368 − ln(e / 6.1121)]

6. Absolute Humidity

AH = 216.7 · e / (273.15 + Tdb) [g/m³]

Assumptions & References

  • Buck equation coefficients from Buck (1981) — accurate to ±0.05 % over −40 °C to 60 °C.
  • Psychrometric constant γ = 0.000665 · P assumes a standard Assmann psychrometer (ventilated).
  • Barometric formula assumes the International Standard Atmosphere (ISA) lapse rate.
  • Magnus inversion uses Lawrence (2005) coefficients (Bull. Amer. Meteor. Soc.).
  • Absolute humidity formula derived from the ideal gas law for water vapour (Mw = 18.015 g/mol).
  • Wet-bulb temperature must be ≤ dry-bulb temperature; both must be in the range −60 °C to 60 °C.
  • Relative humidity is capped at 100 % (supersaturation not modelled).
  • ASHRAE comfort zone: 30 %–60 % RH at 20 °C–26 °C (ASHRAE Standard 55-2020).

In the network