HVAC Load and Duct Sizing Calculator

Calculate the heating/cooling load for a room and determine the required duct diameter or rectangular duct dimensions based on airflow requirements.

Room Load Inputs

Duct Sizing Inputs

Formulas Used

Conduction Load: Q = U × A × ΔT  (BTU/hr)

Infiltration Load: Qinfil = 1.1 × CFMinfil × ΔT  |  CFMinfil = (ACH × Volume) / 60

Total Load: Qtotal = (Qwall + Qceil + Qwin + Qinfil + Qint) × SF  (SF = 1.15 cooling, 1.10 heating)

Required CFM: CFM = Qtotal / (1.1 × ΔTsupply)  (ΔTsupply = 20°F cooling, 30°F heating)

Round Duct Diameter: D = √(4A / π)  where A = CFM / Velocity (ft²)

Rectangular Duct Width: W = A / H  (given duct height H)

Equivalent Diameter (ASHRAE): Deq = 1.30 × (a·b)0.625 / (a+b)0.25

Friction Loss (Darcy-Weisbach approx.): ΔP/100ft = 0.109 × (V/1000)1.82 / D1.22  (in. w.g.)

Assumptions & References

  • Standard air density: 0.075 lb/ft³ at sea level, 70°F (factor 1.1 in sensible heat equation).
  • U-values are representative ranges per ASHRAE 90.1 and IECC; actual values depend on specific construction assemblies.
  • Infiltration ACH: Poor = 1.5, Average = 0.8, Good = 0.5, Excellent = 0.25 (ASHRAE Fundamentals).
  • Occupant sensible heat gain: 250 BTU/hr per person (sedentary, ASHRAE 55).
  • Lighting heat gain: 3.4 BTU/hr per ft² (average residential/light commercial).
  • Supply air temperature differential: 20°F below room for cooling; 30°F above room for heating.
  • Recommended duct velocities: Main trunk 800–1200 FPM; branch ducts 600–900 FPM; residential 400–700 FPM.
  • Equivalent diameter formula per ASHRAE Handbook of Fundamentals, Chapter 21.
  • Friction loss approximation valid for galvanized sheet metal ducts with standard roughness (ε ≈ 0.0003 ft).
  • Safety factors: 15% for cooling, 10% for heating (common industry practice).
  • This calculator provides estimates for preliminary design; a full Manual J/D calculation is required for final system design.

In the network