NEC Panel Schedule Calculator

Calculate panel load schedules per NEC Article 220, including connected loads, demand factors, total load, and minimum service/feeder sizing.

Panel Information

Circuit Loads

Enter each circuit's breaker size and connected load. Select load type for NEC demand factor application.

Additional Loads (NEC 220.14 / 220.82)

Formulas Used

General Lighting Load (NEC 220.12):
VA = Floor Area (sq ft) × 3 VA/sq ft

Lighting Demand Factor (NEC 220.42, Table 220.42):
First 3,000 VA @ 100% + Next 3,001–120,000 VA @ 35% + Remainder @ 25%

Cooking Equipment Demand (NEC Table 220.55, Column C — 1 unit):
≤ 12 kVA → 8 kVA demand; > 12 kVA → 8 kVA + 5% per kW above 12 kVA

Dryer Demand (NEC 220.54):
Demand = max(5,000 VA, Nameplate VA) × 100% (1 unit)

Fixed Appliance Demand (NEC 220.53):
< 4 appliances → 100%; ≥ 4 appliances → 75% of total

Motor Load (NEC 430.24):
Demand = Largest Motor × 125% + Sum of remaining motors × 100%

Non-Coincident Loads — HVAC/Heat (NEC 220.60):
Demand = max(HVAC VA, Electric Heat VA)

Minimum Service Ampacity:
Single-Phase: I = Total Demand VA ÷ Voltage
Three-Phase: I = Total Demand VA ÷ (Voltage × √3)

Assumptions & References

  • Based on NEC 2023 (NFPA 70) standard calculation method (Article 220)
  • Residential occupancy assumed for lighting demand factors (NEC Table 220.42)
  • Minimum 2 small-appliance branch circuits required per NEC 210.11(C)(1)
  • Minimum 1 laundry branch circuit required per NEC 210.11(C)(2)
  • Conductor ampacity from NEC Table 310.16 at 75°C, copper, in conduit
  • Standard service sizes per NEC 230.79: 100, 125, 150, 200, 225, 300, 400A
  • EV charger treated as continuous load at 100% per NEC 625.42
  • Non-coincident HVAC/heat: only the larger load counted per NEC 220.60
  • Motor 125% rule applies to the largest motor only per NEC 430.24
  • Always consult a licensed electrician and local AHJ before installation
  • Optional calculation method (NEC 220.82) may yield lower results for dwellings

In the network